- IP20
- ambient temperature: -40 ° C ... + 75 ° C
- zones; 1,2
- 8 channels for resistance thermometers, remote resistance transmitters, thermocouples, MV transmitters and joysticks
- intrinsic safety entries ex ia with monitoring of line defects
- Module in zone 2 replaceable under tension (hot swap)
(à modifier dans le module "Réassurance")
(à modifier dans le module "Réassurance")
(à modifier dans le module "Réassurance")
The temperature input module 9482 for zone 2 has 8 channels for the ex i operation of resistance thermometers in the circuits with 2, 3 or 4 conductors and thermocouples. DIN, IEC and GOST sensors and resistance transmitters up to 10 kΩ, as well as 4-channel fast-operating joysticles, are supported. The grounded thermocouples can be connected.
| Ambiant temperature | -40 ° C to + 75 ° C |
|---|---|
| Temperature class | T4 |
| Warranty | 2¨ |
| Feed | 24V DC |
| Waterproofing protection (IP) | Ip20 |
| Application / usage | ATEX zone |
| ATEX zone | Zone 1/2 |
| Gas class | IIC |
| ATEX protection mode | Ex i (intrinsic safety) |
| Material | Polyamide |
| Certificat_atex-en_us | DEKRA 13 ATEX 0140 X |
| Certificat_iecex-en_us | IECEX DEK 13.0046X |
check_circle
check_circle
Nous utilisons des cookies tiers pour améliorer votre expérience de navigation, analyser le trafic du site et personnaliser le contenu et les publicités. En savoir plus