- IP20
- ambient temperature: -40 ° C ... + 75 ° C
- Zones: 1.2
- 8 channels for resistance thermometers, remote resistance transmitters, thermocouples, MV transmitters and joysticks
- intrinsic safety entries ex ia with monitoring of line faults and LED error indication
- Module in zone 1 replaceable on tension (Hot swap)
(à modifier dans le module "Réassurance")
(à modifier dans le module "Réassurance")
(à modifier dans le module "Réassurance")
The temperature input module 9482 for zone 1 has 8 channels for the ex i operation of resistance thermometers in the circuits with 2, 3 or 4 conductors and thermocouples. DIN, IEC and GOST sensors and resistance transmitters up to 10 kΩ, as well as 4-channel fast-operating joysticles, are supported. It is possible to connect the thermocouples grounded.
| Ambiant temperature | -40 ° C to + 75 ° C |
|---|---|
| Temperature class | T4 |
| Warranty | 2¨ |
| Feed | 24V DC |
| Waterproofing protection (IP) | Ip20 |
| Application / usage | ATEX zone |
| ATEX zone | Zone 1/2 |
| Gas class | IIC |
| ATEX protection mode | Ex i (intrinsic safety) |
| Certificates | Atex.iecex |
| Material | Polyamide |
| Certificat_atex-en_us | DEKRA 13 ATEX 0140 X |
| Certificat_iecex-en_us | IECEX DEK 13.0046X |
| Body colors | White |