Previous
Next

Logical input / output module for zone 2 Series 9470/33

- IP20
- Ambient temperature: -40 ° C ... 80 ° C
- Zones: 1.2
- 16 channels that can be used in pairs as input or output
- IC IIC intrinsic safety inputs / outputs with line fault monitoring
- Module in zone 2 replaceable under tension (hot swap)
  Garanties sécurité

(à modifier dans le module "Réassurance")

  Politique retours

(à modifier dans le module "Réassurance")

  Politique de livraison

(à modifier dans le module "Réassurance")

 

The 9470/33 logical output / output module for zone 2 has 16 channels that can be used in pairs for Ex i as input for contacts and initiators Namur (EN 60947-5-6) or as output for light lights and Low Power solenoid valves. 8 inputs can be used for frequencies up to 20 kHz, 4 for detecting direction of rotation.
References Manufacturer: 210448
Ambiant temperature -40°C à +80°C
Temperature class T4
Warranty
Feed 24V DC
Protection étanchéité (IP) IP20
Application/Usage Zone ATEX
Zone ATEX Zone 1/2
Classe de gaz IIC
Mode de protection ATEX Ex i (sécurité intrinsèque)
Certificats ATEX.IECEx
Matière Polyamide
Certificat_ATEX-fr_FR DEKRA 12 ATEX0099 X
Certificat_IECEx-fr_FR IECEx DEK 12.0044X
Couleurs corps Blanc
Reference STL0289